Power Cable Accessories

Payment Terms: L/C, T/T, D/P
Power Cable Accessories

Product Description

Power Cable Accessories
Performance Standard: IEC60502.4; GB12706.4
WOER Cold Shrink Terminations kits & Joints
WOER cold shrink cable accessories are manufactured with advanced liquid silicon rubber, which has high resilience and strength, good electrical insulation, is UV stable and adverse to water. The cold shrink cable terminations & joints applications from 1 to 36kV(1kV, 12kV, 15kV, 20kV, 36kV). Most of the cables accessories have passed KEMA type test. The simple installation of cold shrink cables accessories can help you save time and physical force. It improve your work efficiency, make the cables connect safely and reliably, assure your every connection correctly sealed and insulated for long protection. So our cold shrink MV terminations & joints are widely applied in power plant(nuclear), wind farm, substations, city subway etc.

Characteristics:
1). It does not require heating by flaming nor special tools. As long as we pull out the plastic string from silicone rubber tube, the silicone rubber will be tightly shrunk on the needed position.
2). Reliable insulation to ensure superior insulation and high-recovery elasticity; We have adopted imported liquid-silicone rubber, such that the cable will keep its radial pressure permanently, making the contact surface closely jointed together, thus no flash-ores occur, nor strike as well.
3). Superior hermetic sealing: For cable splicing, we have adopted triple hermetic sealing technology and silicone rubber with hermetic and hydrophobic performance; These will be no serious fault due to environmental causes.
4). Easy/convenient installation: By enlarging the dimensions of stress-cone, larger tolerance will be permitted and faults due to installation are reduced to a minimum.
5). Wide usage: Possessing a series of superior performances such as antipollution, long usage, hydrophobic, cold-withstanding etc. The cold shrinkable accessories can be widely used in various regions, especially suitable for high level region, cold weather region, high-humidity region, salt-fog region and high-polluted region, etc.
TYPE/ORDER NUMBER NAME CABLE RANGE
6.35/11kV WLW(N) -3(1)/1  
TERMINATION FOR 6.35/11kV
3(1)CORES CABLE(indoor/outdoor)
25-50mm2
6.35/11kVWLW(N) -3(1)/2 70-120mm2
6.35/11kV WLW(N) -3(1)/3 150-240mm2
6.35/11kV WLW(N) -3(1)/4 300-400mm2
6.35/11kV WLW(N) -3(1)/5 500-630mm2
6.35/11kV WLJ -3(1)/1  
STRAIGHT THROUGH JOINT
FOR 6.35/11kV 3(1)CORES CABLE
25-50mm2
6.35/11kV WLJ -3(1)/2 70-120mm2
6.35/11kV WLJ -3(1)/3 150-240mm2
6.35/11kV WLJ -3(1)/4 300-400mm2
6.35/11kV WLJ -3(1)/5 500mm2
6.35/11kV WLJ -3(1)/6 630mm2
8.7/15kV WLW(N) -3(1)/1  
TERMINATION FOR 8.7/15kV
3(1)CORES CABLE(indoor/outdoor)
25-50mm2
8.7/15kV WLW(N) -3(1)/2 70-120mm2
8.7/15kV WLW(N) -3(1)/3 150-240mm2
8.7/15kV WLW(N) -3(1)/4 300-400mm2
8.7/15kV WLW(N) -3(1)/5 500-630mm2
8.7/15kV WLJ -3(1)/1  
STRAIGHT THROUGH JOINT
FOR 8.7/15kV 3(1)CORES CABLE
25-50mm2
8.7/15kV WLJ -3(1)/2 70-120mm2
8.7/15kV WLJ -3(1)/3 150-240mm2
8.7/15kV WLJ -3(1)/4 300-400mm2
8.7/15kV WLJ -3(1)/5 500mm2
8.7/15kV WLJ -3(1)/6 630mm2
12/20kV WLW(N) -3(1)/1  
TERMINATION FOR 12/20kV
3(1)CORES CABLE(indoor/outdoor)
25-50mm2
12/20kV WLW(N) -3(1)/2 70-120mm2
12/20kV WLW(N) -3(1)/3 150-240mm2
12/20kV WLW(N) -3(1)/4 300-400mm2
12/20kV WLW(N) -3(1)/5 500-630mm2
12/20kV WLJ -3(1)/1  
STRAIGHT THROUGH JOINT
FOR 12/20kV 3(1)CORES CABLE
25-50mm2
12/20kV WLJ -3(1)/2 70-120mm2
12/20V WLJ -3(1)/3 150-240mm2
12/20kV WLJ -3(1)/4 300-400mm2
12/20kV WLJ -3(1)/5 500mm2
12/20kV WLJ -3(1)/6 630mm2
18/30kV WLW(N) -3(1)/1  
TERMINATION FOR 18/30kV
3(1)CORES CABLE(indoor/outdoor)
25-50mm2
18/30kV WLW(N) -3(1)/2 70-150mm2
18/30kV WLW(N) -3(1)/3 185-400mm2
18/30kV WLW(N) -3(1)/4 500-630mm2
18/30kV WLJ -3(1)/1  
STRAIGHT THROUGH JOINT
FOR 18/30kV 3(1)CORES CABLE
50-70mm2
18/30kV WLJ -3(1)/2 95-150mm2
18/30V WLJ-3(1)/3 185-300mm2
18/30kV WLJ -3(1)/4 400-500mm2
18/30kV WLJ -3(1)/5 630mm2
  Test Item 6.35/11(12)kV 8.7/15(17.5)kV 12/20(24)kV 18/30(36)kV IEC 60502.4
1 AC withstand voltage test (in air and ambient temperature) AC for 5 min. at 29kV. No breakdown, No flashover AC for 5 min. at 39kV. No breakdown, No flashover AC for 5 min. at 54kV. No breakdown, No flashover AC for 5 min. at 81kV. No breakdown, No flashover PASS
2 Partial discharge 10pC max. at 11kV 10pC max. at 15kV 10pC max. at 20kV 10pC max. at 31kV PASS
3 Impulse withstand test 10 impulses of each polarity at 75kV 10 impulses of each polarity at 95kV 10 impulses of each polarity at 125kV 10 impulses of each polarity at 170kV PASS
4 Heating cycles
in air
30 cycles at  95º C--100º Cand 16kV in air, No breakdown, No flashover 30 cycles at  95º C--100º Cand 22kV in air, No breakdown, No flashover 30 cycles at  95º C--100º Cand 30kV in air, No breakdown, No flashover 30 cycles at  95º C--100º Cand 30kV in air, No breakdown, No flashover PASS
5 Heating cycles under water 30 cycles at  95º C--100º Cand 16kV under water, No breakdown, No flashover 30 cycles at  95º C--100º Cand 22kV under water, No breakdown, No flashover 30 cycles at  95º C--100º Cand 30kV under water, No breakdown, No flashover 30 cycles at  95º C--100º Cand 30kV under water, No breakdown, No flashover PASS
6 Partial discharge at  95º C--100º C 10pC max. at 11kV 10pC max. at 15kV 10pC max. at 20kV 10pC max. at 31kV PASS
7 Thermal short-circuit (screen) No visible deterioration at 3.0 kA, 1s No visible deterioration at 3.0 kA, 1s No visible deterioration at 3.0 kA, 1s No visible deterioration at 3.0 kA, 1s PASS
8 Thermal short-circuit (conductor) No visible deterioration at 16.8 kA, 2s No visible deterioration at 23.0 kA, 2s No visible deterioration at 31.7 kA, 2s No visible deterioration at 47.5 kA, 2s PASS
9 Dynamic short-circuit No visible deterioration at 59.1 kA, not less than 10 ms No visible deterioration at 81.0 kA, not less than 10 ms No visible deterioration at 112.8 kA, not less than 10 ms No visible deterioration at 167.4 kA, not less than 10 ms PASS
10 Impulse withstand test  at  95º C--100º C 10 impulses of each polarity at 75kV 10 impulses of each polarity at 95kV 10 impulses of each polarity at 125kV 10 impulses of each polarity at 170kV PASS
11 AC withstand voltage test AC for 15 min. at 16kV. No breakdown, No flashover AC for 15 min. at 22kV. No breakdown, No flashover AC for 15 min. at 30kV. No breakdown, No flashover AC for 15 min. at 45kV. No breakdown, No flashover PASS
12 Salt fog
(for outdoor
Terminations only)
1000H at 7.5kV,
no breakdown,
no flashover
 
1000H at 11kV,
no breakdown,
no flashover
 
1000H at 15kV,
no breakdown,
no flashover
 
1000H at 22.5kV,
no breakdown,
no flashover
 
PASS
13 Humidity
(for indoor
terminations only)
1000H at 7.5kV,
no breakdown,
no flashover
 
1000H at 11kV,
no breakdown,
no flashover
 
1000H at 15kV,
no breakdown,
no flashover
 
1000H at 22.5kV,
no breakdown,
no flashover
 
PASS